Cooling Inefficiency Behind Transformer Overheating
50-250 MWFailure RiskTransformer

Cooling Inefficiency Behind Transformer Overheating

Issue

Abnormal behavior was detected in the transformer temperature readings. Possible root causes included oil leakage from the low-voltage bushing joint, hermetic relay oil level reduction, improper sealing in wiping glands, thermal trip failure, or reduced cooling performance due to clogged ventilation components.

Action

Kavaken identified transformer temperature levels that were significantly higher than those of similar turbines, pointing to a cooling issue.

The maintenance team inspected the unit and cleaned the fan ventilation grills. Following the cleaning, the temperature trend declined steadily, confirming that the reduced airflow had been the main cause of overheating.

Impact

100 MWh production loss prevented